LL GLOBAL UA
ZN63A(VS1)-12

ZN63A(VS1)-12

Indoor high-voltage vacuum circuit breaker

Indoor vacuum circuit breaker for three-phase 12 kV, 50 Hz networks, used for protection and control of utility and industrial equipment. Integrated breaker and operating mechanism, available in fixed or withdrawable (truck) versions.

Key parameters

Rated voltage
12 kV
Rated current
630 … 2500 A
Rated short-circuit breaking current
20; 25; 31.5; 40 kA
Mechanical endurance
20,000 cycles

General information

The VS1-12 indoor high-voltage vacuum circuit breaker is indoor switching apparatus designed for three-phase 50 Hz AC networks with a rated voltage of 12 kV. It is used as a protection and control unit for power grid equipment and for power equipment of industrial and mining enterprises. It is suitable for locations requiring frequent operations at rated operating current or frequent breaking of short-circuit currents.

The operating mechanism and the circuit breaker form a single unit: the apparatus can be used as a fixed module or, together with a dedicated truck mechanism, as a withdrawable unit (truck).

Type designation

VS1-12/x-x
VSIndoor high-voltage vacuum circuit breaker
1Design serial number
12Rated voltage, kV
xRated current, A
xRated short-circuit breaking current, kA

Main technical parameters

ParameterUnitValue
Rated voltagekV12
Rated frequencyHz50
Rated insulation levelPower-frequency voltage (1 min)kAto earth / phase-to-phase: 42/48
Lightning impulse (peak)to earth / phase-to-phase: 75/85
Rated short-circuit breaking currentkA202531.540
Rated currentA6306301250160012501600
125012502000250020002500
Rated short-time withstand current (r.m.s.)kA202531.540
Rated peak withstand current (peak)506380100
Rated short-circuit making current (peak)506380100
Rated duration of short circuits4
Mechanical endurancecycles20000
Power-frequency test voltage of secondary circuits (1 min)V2000
Rated operating sequenceO – t – CO – t1 – CO

Service conditions

  • Ambient temperature: not higher than +40 °C, not lower than −15 °C (storage and transport at −30 °C are not permitted).
  • Altitude: not more than 1000 m.
  • Relative humidity: daily average ≤ 95 %, monthly average ≤ 90 %; saturated water vapour pressure: daily average ≤ 2.2×10⁻³ MPa, monthly average ≤ 1.8×10⁻³ MPa.
  • Seismic intensity: not more than 8 degrees.
  • No fire or explosion hazard, severe pollution, chemical corrosion or strong vibration.

Overall and mounting dimensions (mm)

Top — withdrawable version (truck) ZN63A (800) and ZN63A (1000); bottom — fixed version ZN63A (800) and ZN63A (1000). View "A": thread M18×18-6H, hole depth 25.