ZCW10-126

Outdoor compact hybrid switchgear (open-type)

Open-type compact switchgear assembly with air external insulation and SF6 arc quenching for control and protection of three-phase 126 kV networks. The circuit breaker, current transformers and busbars are integrated on a common steel structure, requiring only 30–50 % of the area of a conventional layout.

Key parameters

Rated voltage
126 kV
Rated current
1250 A
Rated short-time withstand current
40 kA
Short-circuit duration
4 s
Bay width
3.3 m (standard)

General information

The ZCW10-126 is an outdoor open-type compact combined switchgear with air external insulation and SF6 as the arc-quenching medium. It is intended for control and protection in three-phase 126 kV AC networks; it can also be used as a bus-section circuit breaker and for switching capacitor banks. Thanks to its compact design, it is optimal for urban, industrial and mountain substations with limited space.

Features

  • The circuit breaker, current transformers, busbars and other components are integrated on an earthed steel support structure — compact design.
  • Occupies only 30–50 % of the area required by a conventional separated layout — significant savings in land and construction costs.
  • The bay is fully assembled, tested and adjusted at the factory and delivered to site as a single unit — installation time is substantially reduced.
  • Proven high-performance interrupter — virtually maintenance-free, high reliability.
  • Bays are connected by factory-made self-supporting busbars — no additional support structures required; flexible layout for various connection schemes.
  • The circuit breaker can be lowered as a whole for repair or replacement; outage time in case of failure is less than 3 hours.

Advantages of the ZCW10-126 configuration

  • Modern self-blast (auto-puffer) interrupter: 25 kA breaking, total break time 3 cycles, simple and reliable design, 20 breaks at full current.
  • The CTB spring operating mechanism meets the "oil-free" switchgear requirement: good mechanical characteristics, compactness, high reliability.
  • Disconnectors with composite insulators, single-column with direct blade rotation — simple and reliable design. Silver-plated copper contacts with graphite coating: high mechanical strength and conductivity, maintenance-free.
  • All exposed metal parts have a modern anti-corrosion coating — rust-free for 20 years under normal pollution conditions.

The ZCW10-126 complies with the requirements of IEC 56, IEC 99-4, IEC 129, IEC 694.

Service conditions

The product is designed for outdoor installation and can also be installed indoors.

  • Altitude: not more than 2000 m (higher on special order).
  • Ambient temperature: −40 °C … +40 °C.
  • Relative humidity: daily average ≤ 95 %, monthly average ≤ 90 % (at 25 °C).
  • Wind speed: ≤ 35 m/s.
  • Pollution level: IV, rated specific creepage distance ≥ 31 mm/kV.
  • Installation site free from flammable, explosive and chemically aggressive substances and severe vibration.
  • Seismic intensity: ≤ 8 degrees.
  • Ice coating thickness: ≤ 10 mm.

Main parameters

ParameterUnitValue
Rated voltagekV126
Rated frequencyHz50
Rated currentA1250
Rated short-time withstand currentkA40
Rated peak withstand currentkA80
Duration of short circuits4
Rated insulation levelLightning impulse withstand voltage (full wave, peak)kV550/630 (across the open gap)
Power-frequency withstand voltage (1 min)kV230/265 (across the open gap)
Control and auxiliary circuit voltageVDC 110, 220; AC 220
Partial discharge levelpC10
Radio interference levelµV≤ 2000
Bay widthm3.3 (standard)