LL GLOBAL UA
SCB10, SCB13

SCB10, SCB13

Cast-resin dry-type transformers

Three-phase dry-type power transformers with epoxy-resin cast windings and foil LV winding. Designed for sites with stringent fire-safety requirements and indoor power distribution systems.

Key parameters

HV voltage class
10 kV
LV voltage
0.4 kV
Rated power
30 … 2500 kVA
Vector group
Yyn0, Dyn11
Short-circuit impedance
4 % / 6 %

General information

The transformers have a wide range of applications and are particularly suitable for sites with stringent fire-safety requirements: mines, oil fields, metro systems, power plants, schools, hospitals, shopping centres, high-rise buildings, as well as any indoor power distribution systems.

SC(B)x-x/10
SThree-phase
CCast resin (epoxy resin encapsulation)
(B)Foil LV winding
xDesign serial number
xRated power, kVA
10HV side voltage class, kV

Service conditions

  • Installation altitude: not more than 1000 m above sea level.
  • Supply voltage waveform: approximately sinusoidal.
  • Symmetry of the polyphase supply voltage: the voltage of the network to which a polyphase transformer is connected should be approximately symmetrical.
  • Ambient temperature: maximum +40 °C; maximum daily average +30 °C; maximum annual average +20 °C; minimum −30 °C (for indoor transformers).

Main technical parameters

Rated power, kVAVoltage combinationVector groupLosses (120 °C), kWNo-load current, %Short-circuit impedance, %Weight, kg
HV, kVHV tapping range, %LV, kVNo-loadLoadOil weightTotal weight
306
6.3
6.6
10
10.5
11
±5
±2×2.5
0.4Yyn0
Dyn11
0.710.191.64250320
5010.271.4370460
631.380.371.2460550
801.570.41.1490580
1001.850.471.0570680
1252.130.541.0640750
1602.520.620.9775890
2002.750.720.88951030
2503.470.880.811001250
3153.990.980.712001350
4004.881.160.714601610
5005.871.340.616801840
6305.961.30.6618001980
8006.951.520.521302310
10008.131.770.4525202720
12509.692.090.4530753300
160011.732.450.4536703900
200014.453.320.444204670
250017.174.00.453105580

Overall and mounting dimensions, mm

8 × Ø20 — mounting holes
Rated power, kVAOverall and mounting dimensions, mm
LWHC1C2
30660450640300400
50770500730400400
63820500770400450
80820500770400450
100880500800400450
125930500830400450
1601000660970550660
20010207501105550660
25011307501140550660
315114075601115550660
40011907501220660660
50012207801280660720
63013508001300660720
80014008001360820820
100014609001450820820
125015709001540820820
1600161010501660820950
2000172010501770950950
2500178010501950950950

Transformer series — product photos

All products