LL GLOBAL UA
RW12-15F

RW12-15F

RW12-15F drop-out fuse cutout with arc chute

Outdoor RW12-15F drop-out fuse cutout protecting distribution transformers and overhead line tee-offs at 12(15) kV against short circuits and overloads. An arc chute made of flame-retardant ABS confines and de-ionises the arc.

Key parameters

Rated voltage
12(15) kV
Rated current
100 / 200 A
Rated short-circuit breaking current
12.5; 16 kA
Rated lightning impulse withstand voltage
125 kV
Creepage distance
330 mm

Design

  1. Upper terminal clamp (3 µm tin plating; double-groove design, integral with the upper contact plate — improved conductivity).
  2. Pressure-relief cap (tin-plated; precision design significantly increases breaking capacity).
  3. Top cover (hot-dip galvanised over 80 µm; integral with the operating hook).
  4. Upper contact plate (3 µm silver plating, integral with the upper terminal clamp — improved conductivity).
  5. Upper moving contact rod (3 µm silver plating, tightly fitted into the cast part in the middle — improved conductivity).
  6. Fuse tube (UV-resistant, non-non-hygroscopic, durable).
  7. Lower fixed contact (3 µm silver plating; prevents lateral swaying of the fuse tube during closing, ensures accurate positioning).
  8. Drop-out mechanism (ensures rapid release of the fuse tube end and reduces the force transmitted to the fuse link during closing).
  9. High-strength insulator (self-cleaning surface, high strength, excellent workmanship).
  10. Arc-quenching grid (high-quality ABS plastic with flame-retardant additives; confines the arc and ensures its de-ionisation).

Note: all iron parts are hot-dip galvanised (coating thickness over 80 µm), fasteners are stainless steel — high-quality grade 304; cast parts — optionally precision-cast brass or aluminium bronze.

Main technical parameters

ParameterUnitRW12RW12
Rated voltagekV12(15)12(15)
Rated currentA100200
Rated frequencyHz5050
Rated current of the baseA100200
Rated short-circuit breaking currentkA/A12.5/100; 16/10012.5/200; 16/200
Power-frequency withstand voltage, wetkV45/5545/55
Power-frequency withstand voltage, drykV50/5550/55
Rated lightning impulse withstand voltagekV125125
Creepage distancemm330330
Mechanical enduranceoperations500500
Altitudem10001000
Ambient temperature°C−40 … +70−40 … +70
Overall dimensionscm60×40×1560×40×15