LW36-126

LW36-126

Outdoor high-voltage AC SF6 circuit breaker

Outdoor SF6 circuit breaker with self-blast arc quenching and spring-operated mechanism for 126 kV, 50 Hz networks. It switches rated and short-circuit currents for line control and protection and can also serve as a bus-coupler breaker.

Key parameters

Rated voltage
126 kV
Rated current
3150 A
Rated short-circuit breaking current
40 kA
Operating mechanism
spring-operated
Mechanical endurance
10,000 operations

General information

LW36-126/3150-40 is a high-voltage AC SF6 circuit breaker with self-blast (self-generated pressure) arc quenching, designed for outdoor installation. It is intended for 50 Hz AC networks with a highest voltage of 126 kV at altitudes up to 2000 m (a version for altitudes above 3000 m is available), at ambient temperatures not below −40 °C and pollution level not higher than IV. It is used to break rated current and short-circuit current or to switch lines, providing control and protection of the power system; it can also be used as a bus-coupler (tie) circuit breaker.

SF6 gas is used as the arc-quenching and insulating medium. The breaker employs state-of-the-art self-blast arc-quenching technology and a new spring operating mechanism. It features long service life, low operating power, low noise and high reliability; simple design, small dimensions and long maintenance intervals. It is in line with the move of power equipment towards oil-free, high-capacity apparatus.

Type designation

LW36-126(W)/T3150-40
LSF6 circuit breaker
WOutdoor installation
36Design serial number
126Rated voltage, kV
(W)Version for polluted areas (reinforced insulation)
TSpring operating mechanism
3150Rated current, A
40Rated short-circuit breaking current, kA

Main technical parameters of the operating mechanism

ParameterUnitValue
Auxiliary circuit voltageVDC 220 or DC 110
Closing and opening coil voltage / currentV/ADC 110/4; DC 220/2
Spring charging motorRated voltageVDC 220, AC 220 / DC 110, AC 110
Normal operating voltage rangeV85 % … 110 %
PowerW600
Spring charging time by motors≤ 15
Heating and lighting circuit voltageVAC 220
Rated voltage of auxiliary contactsVDC 220, AC 220
Rated current of auxiliary contactsA10
Number of auxiliary contacts10 normally open + 10 normally closed

Main technical parameters

ParameterUnitValue
Rated voltagekV126
Rated power-frequency withstand voltageTo earthkVK · 230
Across open contactsK · 265
Rated lightning impulse withstand voltageTo earthK · 550
Across open contactsK · 630
Power-frequency withstand voltage at zero SF6 gauge pressure (5 min)K · 95
Rated frequencyHz50
Rated currentA3150
First-pole-to-clear factor1.5
Rated short-circuit breaking currentkA40
Rated short-circuit making current (peak)kA100
Rated short-time withstand current40
Rated peak withstand current100
Rated duration of short circuits4
Rated out-of-phase breaking currentkA10
Short-line fault breaking currentkA90 % Isc, 75 % Isc
Rated line-charging breaking currentA31.5
Rated operating sequenceO–0.3 s–CO–180 s–CO
Main circuit resistanceµΩ≤ 40
Rated SF6 pressure (gauge, at 20 °C)MPa0.6
Alarm pressure / minimum functional pressure (gauge, at 20 °C)MPa0.55 ± 0.03 / 0.50 ± 0.03
Annual SF6 leakage rate< 0.5 %
Gas moisture content (by volume)≤ 150×10−6
Mechanical enduranceoperations10000
Radio interference levelµV≤ 500
Creepage distanceAcross open contactsmm3906/3150
To earth3906/3150
SF6 mass per circuit breakerkg10
Mass of one circuit breakerkg1500

Note. External insulation is corrected by the altitude factor K: altitude 2000 m — K = 1.13; altitude 3000 m — K = 1.28.