LL GLOBAL UA
LW30-72.5(126)T/T3150-40

LW30-72.5(126)T/T3150-40

Dead-tank SF6 circuit breaker

Outdoor dead-tank SF6 circuit breaker with built-in current transformers and spring-operated mechanism for 72.5 (126) kV, 50 Hz networks. Suited to new and refurbished substations, including seismic regions and cold climates.

Key parameters

Rated voltage
72.5 / 126 kV
Rated current
3150 A
Rated short-circuit breaking current
40 kA
Built-in CT primary current
300 … 2000 A
Mechanical endurance
10,000 cycles

General information

With the development of the power industry, and given that many regions are seismically active or have a cold climate, power systems place ever higher demands on the seismic and low-temperature performance of switchgear; in addition, switching devices are increasingly required to have built-in current transformers. Owing to their design, porcelain-insulated live-tank circuit breakers cannot provide these characteristics either at new substations or in the refurbishment of existing ones. A device is therefore needed that offers high seismic resistance and low-temperature performance, is reliable and economical, and has its own built-in current transformers.

The LW30-72.5(126)T/T3150-40 dead-tank SF6 circuit breaker is a new type of outdoor high-voltage switching device that meets these requirements. It was developed on the basis of many years of experience in high-voltage switching technology and the proven solutions of combined switching devices. It has broad application prospects and is a good choice for new substations and the refurbishment of existing ones.

The LW30-72.5(126)T circuit breaker combines a circuit breaker and current transformers in a single device; the interrupter is mounted horizontally in an earthed aluminium-alloy tank. It is equipped with a CT26 spring operating mechanism. A small number of parts, a simple and compact layout, and a robust, durable design meet the requirements for "oil-free" switchgear; excellent mechanical characteristics and high reliability. All critical parts are machined on CNC machines and machining centres; rolling bearings are used. Mechanical endurance — up to 10,000 operations.

Intended for outdoor three-phase AC 50 Hz high-voltage switchgear — for control and protection in 72.5 (126) kV power transmission and distribution networks; can also be used as a bus-section circuit breaker and for switching capacitor banks.

The product complies with the international standard IEC 62271-100:2001 "High-voltage switchgear and controlgear – Part 100: High-voltage alternating-current circuit breakers". Design, manufacture, inspection, sales and service fully comply with the ISO 9001 quality system, which guarantees the quality of the circuit breaker as a whole.

Service conditions

  • Ambient air temperature: LW30-72.5T — −40 °C … +40 °C (−50 … +40 °C on special order); LW30-126T — −32 °C … +40 °C (−50 … +40 °C on special order).
  • Altitude: ≤ 1000 m (not limited for special orders; bushings are adjusted according to altitude).
  • Air humidity: relative humidity, daily average ≤ 95 %, monthly average ≤ 90 % (25 °C); saturated vapour pressure, daily average ≤ 2.2×10⁻³ MPa, monthly average ≤ 1.8×10⁻³ MPa.
  • Wind speed: ≤ 35 m/s.
  • Ice coating thickness: 20 mm.
  • Seismic intensity: not more than 8 degrees.

Main technical parameters of the circuit breaker

ParameterUnitValue
Rated voltagekV72.5126
Rated currentA3150
Rated short-circuit breaking currentkA40
Rated short-circuit making current (peak)kA100
Rated short-time withstand currentkA40
Rated peak withstand currentkA100
Rated duration of short circuits4
First-pole-to-clear factor1.5
Number of breaks at full rated short-circuit current (cumulative)20
Rated out-of-phase breaking currenttimes10
Short-line fault breaking currentkA30, 36
Rated line-charging breaking/making currentkA31.5
Rated operating sequenceAO – 0.3 s – CO – 180 s – CO
Rated insulation levelLightning impulse withstand voltage (full wave, peak)Phase-to-phase and to earthkV350550
Across the open gapkV410550+100
Power-frequency withstand voltage, 1 minPhase-to-phase and to earthkV160230
Phase-to-phase and to earthkV200230+70
Rated operating times (at rated voltage)msOpening time: 33 ± 6
Closing time: 85 ± 15
Total break timecycles≤ 3
Main circuit resistance per phaseµΩ≤ 280≤ 280
Radio interference levelµV≤ 500
Rated pressureMPa0.380.38
SF6 alarm pressure (20 °C)MPa0.340.34
SF6 lockout pressure (20 °C)MPa0.300.30
Rated voltage of control circuitsVDC 220 / DC 110
Annual SF6 leakage rate/ year≤ 0.3 %
SF6 moisture content (20 °C)µL/L≤ 150 (at commissioning)
≤ 300 (in service)
SF6 masskg3240
Mechanical enduranceoperations10000
CT26 mechanism closing/opening coilsVoltageVDC 220DC 110
Closing coil: current / resistanceA/Ω2.5/88±3 (20 °C)4.4/25±1 (20 °C)
Opening coil: current / resistance2.5/88±3 (20 °C)4.8/23±1 (20 °C)
CT26 mechanism motorVoltageVDC 220AC 220
PowerW600
Dynamic loadHorizontalN20000
Vertical, upward5000
Vertical, downward5000

Circuit breaker assembly and adjustment parameters

ParameterUnitTechnical requirementsMeasurement conditions or method
Pole closing non-simultaneityms≤ 5
Pole opening non-simultaneityms≤ 3
Clearance between output lever roller and cammm1.2 ~ 2.8All measurements with opening and closing springs charged
Opening electromagnet armature travelmm3.4 ~ 5.0
Clearance between opening electromagnet plunger and opening latchmm0.7 ~ 1.2Measured with the mechanism in the "closed" position
Closing electromagnet armature travelmm4 ~ 6
Clearance between latch and closing latchmm1.0 ~ 2.0Measured with the mechanism in the "open" position
Clearance between latch and anti-pumping pinmm1.0 ~ 2.5

Built-in current transformer parameters

Rated primary current, ARated secondary current, ARated output, VAMeasuring winding accuracy class*Measuring winding instrument security factorProtection winding accuracy class
3005300.5(0.2)≤ 510P15
400300.5(0.2)10P15
600300.5(0.2)10P20
800400.5(0.2)10P20
1000500.5(0.2)10P20
1250500.5(0.2)10P20
1600500.5(0.2)10P20
2000500.5(0.2)10P20