LL GLOBAL UA
KYN28-12

KYN28-12

Metal-clad withdrawable switchgear

Indoor metal-clad switchgear with withdrawable vacuum circuit breakers for three-phase 3.6–12 kV, 50 Hz systems. Used for receiving and distributing power and for control, protection and monitoring of circuits, with full mechanical and electrical interlocking.

Key parameters

Rated voltage
3.6; 7.2; 12 kV
Rated current
630 … 3150 A
Rated short-circuit breaking current
20; 25; 31.5; 40 kA
Enclosure degree of protection
IP4X

General information

KYN28-12(Z) (GZS1) is an armoured AC metal-clad switchgear with withdrawable units (hereinafter — switchgear). It is intended for three-phase 50 Hz AC systems: receiving and distributing electrical power, as well as control, protection and monitoring of electrical circuits.

The product complies with IEC 60298 "AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV".

Type designation

KYN28-12-Z
KMetal-clad (armoured)
YWith withdrawable units
NIndoor
28Design serial number
12Rated voltage, kV
ZVacuum circuit breaker

Service conditions

  • Ambient air temperature: maximum +40 °C, minimum −15 °C.
  • Relative humidity: daily average ≤ 95 %, daily average water vapour pressure not more than 2.2 kPa; monthly average ≤ 90 %, monthly average water vapour pressure not more than 1.8 kPa.
  • Altitude: ≤ 1000 m.
  • Seismic intensity: not more than 8 degrees.
  • Ambient air free of noticeable pollution by corrosive or flammable gases, water vapour, etc.
  • Installation site free of severe vibration.
  • Operation under conditions beyond the normal conditions — by agreement when ordering.

Design features

Fully metal, modular, assembled construction. The cabinet enclosure is made of aluminium-zinc coated sheet with high corrosion resistance that requires no additional coating; processed on high-precision CNC equipment using advanced multiple-bending technology, joined with rivet nuts and high-strength bolts — high precision, light weight, good strength.

The switchgear can be equipped with VS1, VD4, ZN65 and other series vacuum circuit breakers — wide compatibility and good interchangeability. The withdrawable truck has a service position and a test position; each position is latched and indicated — safe and reliable.

Up to 9 single-core cables can be connected in the cable compartment. The device is equipped with reliable mechanical and electrical interlocks that fully meet the "five interlocks" requirements. Each compartment has a pressure relief channel for personnel safety.

Main technical parameters

ParameterUnitValue
Rated voltagekV3.6; 7.2; 12
Rated frequencyHz50
Rated current of circuit breakerA630; 1250; 1600; 2000; 2500; 3150
Rated current of switchgearA630; 1250; 1600; 2000; 2500; 3150
Rated short-time withstand current (4 s)kA20; 25; 31.5; 40
Rated peak withstand current (peak)kA50; 63; 80; 100
Rated short-circuit breaking currentkA20; 25; 31.5; 40
Rated short-circuit making current (peak)kA50; 63; 80; 100
Rated insulation level: power-frequency withstand voltage, 1 minPhase-to-phase, phase-to-earthkV24; 32; 42
Across open gapkV24; 32; 42
Lightning impulse withstand voltage (peak)Phase-to-phase, phase-to-earthkV40; 60; 75
Across open gapkV46; 70; 85
Degree of protectionEnclosure — IP4X; between compartments and with the circuit breaker compartment door open — IP2X

Operating mechanism technical parameters

ParameterUnitValue
Rated operating voltageClosing coilVAC/DC 220; 110
Opening coilVAC/DC 220; 110
Coil powerClosing coilW245
Opening coilW245
Spring charging motor powerW50
Rated voltage of spring charging motorVAC/DC 220; 110
Spring charging times≤ 10

All products