LL GLOBAL UA
GGD (GGD1, GGD2, GGD3)

GGD (GGD1, GGD2, GGD3)

Low-voltage AC distribution switchboard

Fixed-type low-voltage switchboards for 380 V, 50 Hz AC systems in power plants, substations and industrial facilities, used for power distribution and control of power, lighting and distribution equipment.

Key parameters

Rated voltage
380 V
Rated current
up to 3150 A
Rated short-circuit breaking current
15 / 30 / 50 kA
Installation
indoor

General information

GGD-type low-voltage AC distribution cabinets are designed for 50 Hz AC distribution systems with a rated operating voltage of 380 V and rated operating current up to 3150 A at power plants, substations, industrial and mining enterprises and other electricity consumers. They are used for conversion and distribution of electric power and for control of power, lighting and distribution equipment.

The GGD cabinet is a new-type low-voltage distribution cabinet developed in line with the requirements of a wide range of electricity users and design institutes, following the principles of safety, economy, rationality and reliability. It features high breaking capacity, good dynamic and thermal stability, flexible electrical schemes, convenient combination, strong serialisation and practicality, a new structure and a high degree of protection. It can be used as a new-generation product to replace outdated low-voltage switchgear assemblies.

GGD cabinets comply with IEC 439 "Low-voltage switchgear and controlgear assemblies".

Type designation

GGDx-xx
GLow-voltage AC distribution cabinet
GFixed mounting of electrical apparatus and fixed connections
DPower distribution cabinet
xDesign serial number: 1 — breaking capacity 15 kA, 2 — 30 kA, 3 — 50 kA
-xMain circuit scheme code
xAuxiliary circuit scheme code

Service conditions

  • Ambient air temperature: not higher than +40 °C and not lower than −5 °C; 24-hour average temperature not higher than +35 °C.
  • Indoor installation and operation; altitude of the installation site not more than 2000 m.
  • Relative humidity of ambient air not more than 50 % at the maximum temperature of +40 °C; higher relative humidity is permitted at lower temperatures (e.g. 90 % at +20 °C). Occasional condensation due to temperature changes should be taken into account.
  • Inclination of the equipment from the vertical when installed: not more than 5°.
  • The equipment should be installed in places free from strong vibration and shocks, where there are no conditions causing corrosion of electrical apparatus.
  • Special requirements — on request when ordering.

Main technical data

ModelRated voltage, VRated current, ARated short-circuit breaking current, kARated short-time withstand current (1 s), kARated peak withstand current, kA
GGD1380A1000151530
B600 (630)
C400
GGD2380A1500 (1600)303063
B1000
C600
GGD3380A31505050105
B2500
C2000

Main circuit schemes

A total of 129 main circuit schemes with 298 versions have been developed for GGD cabinets (not counting schemes and versions derived from changes in auxiliary circuit functions and control voltage), of which:

TypeNumber of main circuit schemesNumber of versions
GGD149123
GGD253107
GGD32768

The main circuit schemes take into account proposals from a wide range of design and operating organisations; schemes required for power plants have been added. Rated current is up to 3150 A; the cabinets are suitable for use with distribution transformers up to and including 2000 kVA. In addition, GGJ1 and GGJ2 capacitor compensation cabinets have been developed for reactive power compensation: 4 main circuit schemes, 12 versions in total.