LL GLOBAL UA
FKN12-12 · FKRN12-12

FKN12-12 · FKRN12-12

Indoor air-blast (puffer) load break switch

Indoor 12 kV load break switch with compressed-air (puffer) arc quenching, switching load, closed-loop, transformer magnetising and charging currents. FKRN12-12 is a switch-fuse combination capable of interrupting any current up to the short-circuit current.

Key parameters

Rated voltage
12 kV
Rated current
630 A (FKN12-12); 100 A (FKRN12-12)
Rated short-time withstand current
20 kA (4 s)
Rated short-circuit breaking current (FKRN12-12)
31.5 kA

General information

The FKN12-12 is an indoor high-voltage puffer-type (compressed-air arc-quenching) load break switch: a three-phase switching device rated for 12 kV and 50 Hz. It is intended for making and breaking load currents, closed-loop currents, magnetising currents of unloaded transformers and charging currents, as well as for making onto a short-circuit current. The load break switch, fitted with an earthing switch, withstands short-circuit current.

The FKRN12-12 is an indoor load break switch–fuse combination that combines the FKN12-12 load break switch with SKLAJ-12 (XRNTC1-10) current-limiting high-voltage fuses. It reliably breaks any current up to the short-circuit current: the load break switch breaks operating currents, the fuse breaks the short-circuit current, and any current between the operating current and the full short-circuit current is broken jointly — the fuse, via its striker, trips the load break switch.

Type designation

Note: the spring operating mechanism is available in two versions — manually operated and electrically (motor) operated.

Service conditions

  • Air temperature: −25 °C … +40 °C.
  • Altitude: not more than 1000 m.
  • Relative humidity: daily average ≤ 95 %, monthly average ≤ 90 %.
  • Seismic intensity: not more than 8 degrees.
  • Installation site: free from fire and explosion hazards, chemical corrosion and severe vibration.
  • Pollution level: II.

Main technical parameters

ParameterUnitFKN12-12FKRN12-12
Rated voltagekV12
Rated frequencyHz50
Rated currentA630100
Lightning impulse withstand voltagekVto earth and phase-to-phase — 75; across the isolating distance — 85
Power-frequency withstand voltage (1 min)kVto earth and phase-to-phase — 42; across the isolating distance — 48
Rated short-time withstand currentkA20 (4 s)
Rated peak withstand currentkA50
Rated making current (peak)kA5050
Rated short-circuit breaking current (prospective)kA31.5
Maximum Joule integral I²t when breaking the critical currentA²·saccording to fuse characteristic
Minimum breaking currentkAaccording to fuse characteristic
Rated transfer currentkA1.5
Maximum breaking current (reference value)kA1.8
Breaking capacity for unloaded transformerkVA1250
Rated cable-charging breaking currentA10
Number of breaks at rated active load currenttimes> 100
Time from striker operation to load break switch openings> 0.06
Earthing switch short-time withstand currentkA20 (2 s)
Earthing switch short-time withstand current (peak)kA50
Motor operating mechanism supply voltageVAC/DC 110, 220

Overall and mounting dimensions (mm)

Note: dimension L or L1 in the drawing may be specified by the customer; standard L = 174 mm.